......@@ -36,8 +36,16 @@ $| = 1; # Turn off line buffering on output
use SNMP;
use strict;
#
# XXX for configurations in which APC unit always returns error
# even when it works.
#
# NOTE: You can probably fix such units by instead making sure the
# controller uses the 'rPDUOutletControlOutletCommand' OID in power() below.
# The default 'sPDUOutletCtl' will work on these controllers but will return
# a '' status. I would guess that everything running "masterSwitch.6" and
# later should be using the newer OID.
#
my $ignore_errors = 0;
sub new($$;$) {
......@@ -103,10 +111,10 @@ sub power {
if ($type eq "masterSwitchrPDU") {
$oids = $CtlOIDS{"rPDU"};
}
# XXX the AP8941 power controllers we have need to use this OID
# else they return an error on set operations (though the operations
# do work!)
elsif ($type eq "masterSwitch.6") {
# XXX newer APC power controllers we have (AP8941, AP7900B) need to
# use this OID else they return an error on set operations (though
# the operations do work!)
elsif ($type eq "masterSwitch.6" || $type eq "masterSwitch.8") {
$oids = $CtlOIDS{"rPDU"};
}
}
......